<< Click to Display Table of Contents >> Total Building Sensible Heat Gain Due to Infiltration or Ventilation |
Qsi = 1.1 x ACF x CFMi x STD
Qsv = 1.1 x ACF x CFMv x STD
Where:
Qsi = Sensible heat gain due to infiltration, Btuh
Qsv = Sensible heat gain due to ventilation, Btuh
CFMi = Flow of infiltration air, CFM
CFMv = Flow of ventilation air, CFM
ACF = Altitude correction factor from Table 10B, dimensionless
STD = Outdoor design temperature minus indoor design temperature, oF
1.1 = A constant, Btuh/CFM-F
Ref: Manual J 8 - Page 8-7