<< Click to Display Table of Contents >> Total Building Latent Heat Gain Due to Infiltration or Ventilation |
QLi = 0.68 x ACF x CFMi x GrDiff
QLv = 0.68 x ACF x CFMv x GrDiff
Where:
Qli = Latent heat gain due to infiltration, Btuh
Qlv = Latent heat gain due to ventilation, Btuh
CFMi = Flow of infiltration air, CFM
CFMv = Flow of ventilation air, CFM
ACF = Altitude correction factor from Table 10B, dimensionless
GrDiff = Grains of moisture difference between the outside and inside air
0.68 = A constant, Btuh/CFM-Grain
Ref: Manual J 8 - Page 8-7