<< Click to Display Table of Contents >> Total CFM Requirement for Cooling |
CFMs = Qs / (1.1 x AF x CTD)
Where:
CFMs = Total cooling supply air required for the building, CFM
Qs = Total sensible heat gain on building, Btuh
1.1 = A constant, Btuh/CFM-oF
AF = Altitude Factor
CTD = Room design temperature minus temperature of air leaving the cooling coil, oF
AF = [(1 - 6.8745 x 10-6 x E)5.2561] x 14.696 x 2.036 / 29.921
Where:
E = Elevation, feet
14.696 = Atmospheric pressure at sea level, psia
2.036 = A constant, inch Hg/psia
29.921 = Barometric pressure at sea level, inches Hg
Ref: (GRP-158) - A.69