<< Click to Display Table of Contents >> Heat Gain for Glass Shaded by an Overhang |
Qsgs = (Hu x W x HTM-Ns) + [(Ht-Hu) x W x HTMs]
Where:
Qsgs = Cooling load due to glass section shaded by overhang, Btuh
Hu = Height of unshaded portion of glass, feet
W = Width of glass, feet
HTM-Ns = Heat transfer multiplier for north facing glass, (Table 3, Manual J 8), Btuh/Sq.Ft.
Ht = Total height of glass, feet
HTMs = Heat transfer multiplier for glass facing normal direction, (Table 3, Manual J 8), Btuh/Sq.Ft.
Ref: Manual J 8 - Page 6-9
Note: If the glass faces north, the overhang has no effect.